NSN 6665-01-530-2725
Part Details | AUTOMATIC GAS ALARM
6665-01-530-2725 A device which detects the presence of hazardous gases or vapors, toxic explosives, and/or sounds an alarm, and/or lights or flashes lights of distinctive color when the concentration reaches a dangerous level. Excludes ALARM, CHEMICAL AGENT, AUTOMATIC.
Alternate Parts: CM21A, CM-21A, MACM6, MA-CM6, CM21A, CM-21A, 6665-01-530-2725, 01-530-2725, 6665015302725, 015302725
Supply Group (FSG) | NSN Assigned | NIIN | Item Name Code (INC) |
---|---|---|---|
66 | MAY 19, 2005 | 01-530-2725 | 28625 ( ALARM, GAS, AUTOMATIC ) |
REFERENCE DRAWINGS & PICTURES
Cross Reference | NSN 6665-01-530-2725
Part Number | Cage Code | Manufacturer |
---|---|---|
CM-21A | 76381 | 3M COMPANYDBA 3M |
MA-CM6 | 76381 | 3M COMPANYDBA 3M |
CM-21A | 2Y359 | AERION TECHNOLOGIES, INCDBA MACURCO |
Technical Data | NSN 6665-01-530-2725
Characteristic | Specifications |
---|---|
MEDIA DETECTED | CARBON MONOXIDE |
USAGE DESIGN | INDUSTRIAL |
SPECIFIC USAGE DESIGN | DESIGNED FOR CO DETECTION AND AUTOMATED EXHAUST FAN CONTROL IN AUTOMOTIVE MAINTENANCE FACILITES, ENCLOSED PARKING GARAGES, WAREHOUSES WITH FORKLIFTS, ETC. |
INDICATOR TYPE | KG ANY ACCEPTABLE AND DP ANY ACCEPTABLE |
DESIGN TYPE | NONTRIPOD MOUNTING |
SPECIAL FEATURES | CM-21A ACTIVATES FAN RELAY AT 35 PPM OF CO AVERAGED OVER 5 MINUTES. (25 PPM IS SELECTABLE) ALARM RELAY WILL BE ACTIVATED AT 100 PPM OF CO AFTER 30 MINTUTES OR 200 PPM AFTER 10 MINUTES. 5 AMP SPDT FAN RELAY CONTROLS STARTERS OF EXHAUST FANS. A 0.5 AMP N.O. ALARM RELAY CONNECTS TO WARNING DEVICES OR CONTROL PANELS. |
CUBIC MEASURE | 38.250 CUBIC INCHES |
SUPPLEMENTARY FEATURES | DIMENTIONS ARE 4.5 X 4 X 2.125 INCHES. ITEM SHOULD BE MOUNTED 4 TO 5 FEET ABOVE FLOOR LEVEL. |
PART NAME ASSIGNED BY CONTROLLING AGENCY | CARBON MONOXIDE DETECTOR AND CONTROLLER |