NSN 6115-00-133-9104

Part Details | DIESEL ENGINE GENERATOR SET

6115-00-133-9104 A generator set using a diesel engine as the prime mover. Excludes GENERATOR SET, DIESEL ENGINE, TRAILER MOUNTED.

Alternate Parts: MEP009A, 70009, 70-009, 043060660, 04306-0660, 043060660, 04306-0660, 6115-00-133-9104, 00-133-9104, 6115001339104, 001339104

Supply Group (FSG) NSN Assigned NIIN Item Name Code (INC)
61SEP 11, 196800-133-910400476 ( GENERATOR SET, DIESEL ENGINE )
REFERENCE DRAWINGS & PICTURES
Cross Reference | NSN 6115-00-133-9104
Part Number Cage Code Manufacturer
MEP009A30554DEPARTMENT OF DEFENSE PROJECTMANAGER-MOBILE ELECTRIC POWER
70-00930554DEPARTMENT OF DEFENSE PROJECTMANAGER-MOBILE ELECTRIC POWER
04306-066093568HARSCO CORPBMY-COMBAT SYSTEMS DIV
04306-066079343SCIENCE APPLICATIONS INTERNATIONALCORPORATION
Technical Data | NSN 6115-00-133-9104
Characteristic Specifications
CURRENT TYPE AC
AC WATTAGE RATING200.0 KILOWATTS AND 200.0 KILOWATTS AND 200.0 KILOWATTS AND 167.0 KILOWATTS AND 167.0 KILOWATTS
FREQUENCY RATING50.0 HERTZ MINIMUM AND 60.0 HERTZ MAXIMUM
PHASE THREE
LINE TO LINE VOLTAGE IN VOLTSB480.0$$B416.0$$B208.0$$B416.0$$B208.0
LINE TO NEUTRAL VOLTAGE IN VOLTSB277.0$$B240.0$$B120.0$$B240.0$$B120.0
POWER FACTOR IN PERCENTB80.0$$B80.0$$B80.0$$B80.0$$B80.0
EXCITOR TYPE SELF-EXCITED
EXCITOR INCLUDED
AMBIENT TEMP IN DEG CELSIUS51.7
TEMP RISE RATING IN DEG CELSIUS FOR CONTINUOUS OPERATION50.0
PRIME MOVER COOLING MEDIUM LIQUID
COOLING METHOD RADIATOR
PRIME MOVER STARTING METHODC ANY ACCEPTABLE
CRANKING VOLTAGE IN VOLTS24.0
AUTOMATIC STARTING FEATURE NOT PROVIDED
MOUNTING TYPE SKID
OVERALL LENGTH114.000 INCHES NOMINAL
OVERALL WIDTH50.000 INCHES NOMINAL
OVERALL HEIGHT75.000 INCHES NOMINAL
RADIO INTERFERENCE SUPPRESSION INCLUDED
WINTERIZATION FEATURE NOT INCLUDED
HOUSING TYPE INCLOSED
INCLOSURE TYPE FULLY INCLOSED
ITEM NAME ASSIGNED BY GOVERNMENT AGENCYGENERATOR SET,DIESEL ENGINE